► Specifications
|
Supported Baud Rates:
|
9600, 19200, 38400, 57600, 76800, 115200.
|
|
Data Size:
|
8.
|
|
Parity:
|
None.
|
|
Stop Bits:
|
1
|
|
Service:
|
Air and non-combustible, compatible gases.
|
|
Wetted Materials:
|
Consult factory.
|
|
Accuracy:
|
±1% FS for 0.15 in w.c. (40 Pa), 0.25 in w.c. (50 Pa), 0.5 in w.c. (100 Pa), 2 in w.c. (500 Pa), 3 in w.c. (750 Pa), 5 in w.c. (1250 Pa), 10 in w.c. (2 kPa), 15 in w.c. (3 kPa), 25 in w.c. (5 kPa), 28 in w.c. (6.975 kPa) ±2% FS for 0.1 in w.c. (25 Pa), 1 in w.c. (250 Pa), and all bi-directional ranges.
|
|
Stability:
|
±1% / year FSO.
|
|
Temperature Limits
|
0 to 150°F (-18 to 66°C).
|
|
Pressure Limits:
|
1 psi max., operation 10 psi burst.
|
|
Power Requirement:
|
10 to 35 VDC (2-wire), 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire).
|
|
Output Signals:
|
4 to 20 mA (2-wire), 0 to 5 VDC, 0 to 10 VDC (3-wire).
|
|
Response Time:
|
Adjustable: 0.5 to 15 sec. time constant. Provides a 95% response time of 1.5 to 45 seconds.
|
|
Zero & Span Adjustments:
|
Digital push button.
|
|
Loop Resistance:
|
Current Output: 0 to 1250 Ω max
Voltage Output: Min. load resistance 1 kΩ.
|
|
Current Consumption:
|
40 mA max.
|
|
Display (optional):
|
5 digit LCD.
|
|
Electrical Connection:
|
3-wire removable European style terminal block for 16 to 22 AWG.
|
|
Electrical Entry:
|
1/2″ NPS thread.
|
|
Process Connection:
|
3/16″ ID tubing (5 mm ID) Max. OD 9 mm.
|
|
Enclosure Rating:
|
IP66.
|
|
Mounting Orientation:
|
Diaphragm in vertical position.
|
|
Weight:
|
8.0 oz (230 g).
|
► Application
- Monitoring of static pressure in wind pipes
- Monitor the sieve status in the AHU
- Room pressure monitoring in pharmaceutical and electronic charging room applications
- Measure wind speed / flow rate in VAV system